- Type LW3-12/630-20 column-mounted circuit breakers are suitable for use with a rated voltage of 12kV.
- Rated current 630A, 50/60Hz distribution network off.
- Turning off the load current and overload current in the power system can automatically separate the fault distribution circuit segments.
- Switches with the latest technology of electronic controller, manual operation, electric operation and remote operation.
- The electronic controller is housed in a stainless steel case and can be used in all weather conditions.
- In addition, the box can also be installed with wired and wireless modems, which can achieve remote monitoring and control.
- Simple column installation and arrangement is convenient and fast, reducing the construction cost.
Performance advantages:
1. SF6 gas is non - toxic, non - flammable electrical insulation gas, with excellent arc - extinguishing characteristics.
2. A variety of options are available in addition to standard ceramic bushing, including rubber insulators on epoxy equipment bushing.
3. The color-coded primary contact position indicator is easy to see from the ground(Green-open;Red-close).The indicator is directly connected to the main contact drive shaft assembly,to ensure accurate display of contact status.
4. Spring energy storage mechanism ensures fast closing and opening operation(less than 110ms).
5. Standby electronic controller, not only local operation, but also FTU/RTU interface to achieve the main console operation.
6. Switches are made of proven rugged, corrosion resistant materials(304L stainless steel plate for warships).To ensure the life is long(30 years),and to achieve a series of operation.It has the desired characteristics of column mounted equipment.
7. Every switches have been filled with SF6 gas and finished sealing treatment before shipping.And been tested according to IEC60265-1(1988),GB3804-1990 standard.
1. Ambient air temperature: upper limit +50℃, lower limit -40℃.
2. Relative humidity: 110%
3. Altitude: Not over 3000m.
4. Wind pressure: not over 700pa(equivalently wind speed 34m/s).
5. Seismic intensity: 8 degrees.
6. Installation site: no fire,no explosion.
No chemical corrosion and frequent violent vibration.
7. Class of pollution:Ⅲ,Ⅳ.
Rated parameters |
Other technical parameters |
Power frequency withstand voltage |
|||
The rated voltage |
12kV |
Internal arc test |
20kA/0.1sec |
10sec (wet test) |
45kV |
Rated current |
630A |
Arc suppression medium |
SF6Gas |
1min (dry test) |
50kV |
Rated frequency |
50/60Hz |
Insulating medium |
SF6Gas |
1min (dry test) |
50kV |
Short-time Tolerance Current (RMS) |
20kA/4sec |
Creep distance (porcelain casing) |
550mm |
||
Creep distance (silicone sleeve) |
615mm |
||||
Protection grade |
54 |
||||
|
|||||
Mechanical properties |
Impact pressure (1.2×50μs) |
Gas pressure |
|||
Closing/opening time |
<0.1sec |
Relatively |
85kV |
rated working pressure(kgf/cm2G,at20oC) |
0.7 |
Mechanical stability operation |
10,000 times |
Between the fracture |
95kV |
Explosion-proof device operating pressure(kgf/cm2G) |
4~6 |
Ambient temperature |
-25(-40)~70oC |
|
|
minimum operating pressure(kgf/cm2G) |
0.05 |
|
|
|
|
Gas leakage rate(cc/sec) |
1.1×10-7 |