Main technical parameters of ZN73-12 vacuum circuit breaker
Item | Unit | VN3-12 | VS1-12 | ||
Rated voltage | KV | 12 | |||
1min power frequency withstand voltage | KV | 42 | |||
Lightning impulse withstand voltage | KV | 75 | |||
Rated frequency | Az | 50 | |||
Rated current Rated short-circuit breaking current Rated short-circuit making current (peak) 4s rated short-time withstand current Rated peak withstand current |
A |
630、1250 20、25、31.5 50、63、80 20、25、31.5 50、63、80 |
1600-3150 31.5、40 80、100 31.5、40 80、100 |
||
Rated breaking current of back-to-back capacitor | A |
400 |
|||
Rated breaking current of single capacitor bank | A |
630 |
|||
Operating sequence |
O-0.3S-CO-180s-CO |
||||
Breaking current times | Times |
30 |
|||
Mechanical life |
10000 |
||||
Rated tripping current | A |
5 |
|||
Rated operating voltage |
Closing coil Opening coil |
V |
DC220、AC220 |
||
Circuit resistance | uΩ |
≤35 |
≤40 |
Item | Unit |
GN19-12C/630 GN30-12/630 GN30-12D/630 |
GN19-12C/1000 GN30-12/1000 GN30-12D/1000 |
GN19-12C/1250 GN30-12/1250 GN30-12D/1250 |
2000 GN30-12/1250 3150 |
Rated voltage | KV |
12 |
|||
1min power frequency withstand voltage | KV |
42 |
|||
Lightning impulse withstand voltage (phase-to-phase, phase-to-ground / isolating distance) |
KV |
75/85 |
|||
Rated current | A | 630 | 1000 | 1250 | 2000-3150 |
4s short-time withstand current Rated peak withstand current |
KA KA |
20 50 |
31.5 |
40 100 |