It is applicable for power systems of AC50Hz and rated working voltage 35kV, used as transformation equipment for substations of 35kV.
Iron
The iron core is made of cold-rolled grain-oriented silicon steel sheets with high magnetic conductivity, with inclined joint laminated structure. Section of the core limbs is of multi-class ladder round, with uniform section with that of yoke.
Winding
The winding adopts corrugated oil duct with non-dipping process, bound by shrinkable tape; all windings are of concentric coils; taps of HV winding with corresponding tapping voltage shall be led to the tap switch, and the switch shall be installed on the box cover. Power supply must be cut off first when changing the tapping voltage.
Installation of protection device
●Transformers of all capacity specifications have been equipped with pressure relief valve;
●Gas relay with alarm and tripping terminals is available on request.
Oil-temperature measurement device
●All the transformers are equipped with tube holder for glass-stem thermometer that is set on the top of oil tank, and immersed in oil for about 120±10mm;
●1000~2000kVA transformer is equipped with outdoor signal thermometer;
Transformer oil tank
●Transformer oil tank is composed of corrugated walls with powder painted surface and reinforced with film. Corrugated cooling fin not only has cooling function, but also has “breathing” function, the elasticity of corrugated cooling fin make it adapt to the change of oil volume due to change of temperature. So this hermetically sealed transformer does not have oil conservator, which decreases the height of transformer.
●The transformer adopts vacuum oil-injection technology during encapsulation that thoroughly removes the moisture from transformer, and keeps the transformer oil from contacting the air. This technology also avoid insulation performance reduction or oil aging due to entering of oxygen or moisture, it improves operation reliability of transformer.
● Installation height: altitude shall not exceed 1000m
● Ambient temperature: -40℃~40℃
Rated capacity
|
Installation dimension(mm)
|
kVA
|
L
|
W
|
H
|
C1
|
C2
|
50
|
1140
|
915
|
1430
|
550
|
550
|
100
|
1140
|
1040
|
1550
|
550
|
550
|
125
|
1140
|
1040
|
1580
|
550
|
550
|
160
|
1660
|
880
|
1620
|
660
|
660
|
200
|
1660
|
890
|
1650
|
660
|
660
|
250
|
1660
|
900
|
1690
|
660
|
660
|
315
|
1745
|
920
|
1760
|
660
|
660
|
400
|
1785
|
1000
|
1810
|
660
|
660
|
500
|
1815
|
1100
|
1850
|
820
|
820
|
630
|
1830
|
1115
|
1920
|
820
|
820
|
800
|
1905
|
1230
|
1960
|
820
|
820
|
1000
|
2260
|
1250
|
2135
|
820
|
820
|
1250
|
2415
|
1320
|
2165
|
820
|
820
|
1600
|
2505
|
1450
|
2235
|
820
|
820
|
S9-50 ~ 1600/35 transformers
Rated capacity
|
Voltage combination
|
Connection group
|
Loss (KW)
|
No-load current
|
Short-circuit impedance
|
Weight (kg)
|
kVA
|
HV kV
|
High-voltage tapping range
|
LV kV
|
symbol
|
No-load
|
On-load
|
%
|
%
|
Oil weight
|
Gross weight
|
50
|
35
38.5
|
±5%
±2×2.5%
|
0.4
|
Dyn11
Yyn0
|
0.21
|
1.27/1.21
|
2
|
6.5
|
220
|
610
|
100
|
0.29
|
2.12/2.02
|
1.8
|
250
|
810
|
125
|
0.34
|
2.50/2.38
|
1.7
|
255
|
885
|
160
|
0.36
|
2.97/2.83
|
1.6
|
305
|
1040
|
200
|
0.43
|
3.50/3.33
|
1.5
|
403
|
1400
|
250
|
0.51
|
4.16/3.96
|
1.4
|
412
|
1450
|
315
|
0.61
|
5.01/4.77
|
1.4
|
430
|
1600
|
400
|
0.73
|
6.05/5.76
|
1.3
|
460
|
1700
|
500
|
0.86
|
7.28/6.93
|
1.2
|
525
|
2025
|
630
|
1.04
|
8.28
|
1.1
|
580
|
2315
|
800
|
1.23
|
9.9
|
1
|
645
|
2715
|
1000
|
1.44
|
12.15
|
1
|
745
|
3315
|
1250
|
1.76
|
14.67
|
0.9
|
825
|
3730
|
1600
|
2.10
|
17.55
|
0.8
|
955
|
4420
|
Note: load loss values above the oblique line in the table are suitable for products of connection group Yd11, and values below are suitable for products of connection group YNd11.
Order guide
Please specify the product model, rated capacity, HV/LV rated voltage and high-voltage tapping range, phase number, frequency, connection group symbol and so on in the order.