Input |
Voltage stabilization range |
Three-phase 304V-456V, single-phase 176V-264V |
Frequency | 50HZ/60HZ | |
Output | Rated voltage | Phase voltage 220V, line voltage 380V |
Center voltage | ±7% | |
Accuracy of voltage stabilization |
±5% | |
Response time | ≤50ms | |
Waveform distortion | No additional waveform distortion (static) | |
Efficiency | ≥98% | |
Three-phase unbalanced degree |
Three-phase voltage balance automatically | |
Time delay output | Voltage stabilization output first (protect equipment from impact) | |
Over-voltage |
When output phase voltage is beyond 10% (245), it cuts off the output, or turns to bypass uninterruptedly |
|
Under-voltage |
When output phase voltage is lower than 10% (198), it cuts off the output, or turns to bypass uninterruptedly |
|
Protection | Open-phase | With automatic cut off function |
Overload | Electronic detector, cut off the output in 3min in case of overload | |
Over-current | Dual protections of electronic detector and circuit breaker | |
Short-circuit | Dual protections of electronic detector and circuit breaker | |
Bypass | By manual, or automatic bypass uninterruptedly | |
Indicator | Voltage | A, B, C and ΣABC three phases have TRMS digital display respectively |
Current | A, B, C and ΣABC three phases have TRMS digital display respectively | |
Working status | Voltage stabilization status and utility power status | |
Abnormal | Over-voltage, under-voltage, overload, fuse blowout | |
Working mode | Two modes: voltage stabilization and utility power | |
Overload capacity | 5 times the rated current for 1s |